9
6. Reset to default values
Menu level
parameterization level
Setting the code,
CODE:
Default:
1234
With this setting it is possible to select an individual code (factory setting
1 2 3 4
) for the
programming lock. For programming lock/unlock please proceed according to menu item
run
.
Number of additional supporting points,
SPCt:
Default:
0
8 support points can be defined in addition to the start and end values in order to linearize non-
linear sensor values. Only the activated support point parameters are displayed.
Display value for supporting points,
dIS1 … dIS5:
Under this parameter the interpolation points are defined in terms of values. With sensor
calibration, as with end value/offset, you are asked at the end whether a calibration is to be
triggered.
Analogue values for supporting points,
INP1 … INP8:
The supporting points are always specified according to the selected input signal mA/V. Here
the desired analog values can be freely parameterized in ascending order.
6. Reset to default values
To set the device to a defined basic state, it is possible to perform a reset to the default values.
For this purpose, the following procedure shall be applied:
• Switch off the voltage supply of the device
• Press
[P]
key
• Switch on the power supply and press the
[P]
key until the display shows "- - - -"..
Reset loads the default values and uses them for further operation. This returns the device to the state it was
in on delivery.
ATTENTION!
•
All application specific data is lost.