5-84
PFC-6030 • 5403595 • REV C-1 • 10/13
Programming Modules
This section addresses how to program optional all P-Link appliances, including the DACT (UD-1000), RA-6500, RA-6075,
CA-6075 Class A expansion card, LED-16 annunciators, and others.
CA-6075 Class A Converter Module
The PFC-6030 supports one (1) Class A Expander card.
To add and configure a Class A module:
1. Select
Class A Card
from the system panel.
2. Click the
Add Device button
. The
“Add Device” window
displays.
Figure 118. CA-6075 Class A – Add Device Window
Note
: If you attempt to add more than one (1) Class A card, an error dialog box displays, as shown below:
Figure 119. Unable to Add Dialog Box
3. Double-click in the
“SLC Class” field
to select class type (A or B).
4. Double-click in the
“P-Link Class” field
to select class type (A or B).
Remote Annunciators (RA-6500 and RA-6075)
The PFC-6030 supports up to thirty-one (31) remote annunciators in any combination of RA-6500 and RA-6075. Each LCD
annunciator may be programmed with a unique name to help identify the location of an “
off normal”
condition.
To add and configure a remote annunciator:
1. Select
Annunciators
from system panel.
2. Click the
Add Device button
to display the
"Add Device” window
.
Figure 120. Example of the Add Annunciator Device Window
3. Double-click in the
“Name” field
to customize name.
4. Double-click in “
Address” field
to adjust address, if needed.
5. Repeat steps, as needed, to continue adding annunciators.