Cross Zone Configurations
The purpose of creating cross zones is to ensure that two (2) or more separate zones are activated before an output zone is
triggered.
Although crossing two (2) zones is the most common configuration, up to eight (8) zones may be combined. In this case, when all
the zones that have been crossed are active, the specified outputs will be activated.
To create a cross zone:
1. Create two or more (
“Alarm” or “Supervisory” type
) zone(s) and name appropriately.
2.
Configure and name devices.
3. Move devices into zones.
4. Open the
Cross Zones window
. Click in the
“Enabled” box
.
Figure 117. Cross Zones Window Showing Enabled
Note:
If the “Enabled” option is
not selected, the cross zone relationship will not be in effect.
5. Click on the drop down arrow in the
“Input Zone 1” field
. All available zones display.
6. Click to select input zone.
7.
Repeat steps for the next field, “
Input Zone 2” field.
8. Click on drop down arrow in the “
Output Zone” field.
Select output zone.