5-41
PFC-6030 • 5403595 • REV C-1 • 10/13
Section 5: Programming
This section addresses programming options and their parameters, provides an overview of the programming process, and
addresses how to use the two programming methods: (1) the
LEARN
function, and (2) the
remote computer programming
process
.
This section also includes procedures on uploading and downloading configuration data using the
panel configuration software
.
Please refer to this section to learn how to navigate within the software, access and modify programming settings, such as the
system clock and day/night mode sensitivity settings, scheduling holidays, displaying events, and programming optional modules
(
i.e., a DACT, remote and LED annunciators, and a Class A card
).
Programming Options
Table 9: Programming Options
Topic
Feature or
Option
Permitted
in UL (Y/N)
Possible Settings
Setting(s) Permitted
in UL864?
Comment
Misc
Idle LCD
Message
Y
Yes/No
All settings allowed
Misc
Display Events
Y
Initial Event
Newest Event
Initial Event
Auto display of
first event
Misc
SLC Blink
Y
Normal/Slow/Off
All settings allowed
Misc
Alarm
Verification Time
Y
0-60 Sec
All settings allowed
Misc
Waterflow Delay
Y
0-255 Sec
0-90 sec
Misc
AC Report Delay
Y
0-30 Hours
1-3 Hours
For UL864 use 1-3 Hr
Misc
DH Low AC
Dropout Delay
Y
No delay, 15 sec, 1 minute,
5 minute
All settings allowed
Misc
Auto Test Time
Y
Time of Day
All settings allowed
Misc
Strobes Active
When Silenced
Y
Yes/No
All settings allowed
Misc
50 Hz AC
Y
Yes/No
All settings allowed
Misc
Display AM/PM
Y
AM/PM, 24 Hour
All settings allowed
Misc
Time Zone
Y
24 Time Zone Selections
All settings allowed
Misc
DST Enabled
Y
Yes/No
All settings allowed
Misc
DST Start
Y
Month/Day
All settings allowed
Misc
DST End
Y
Month/Day
All settings allowed
To users, installers, authorities having jurisdiction, and other involved
parties:
This product incorporates field-programmable software. In order for the
product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, certain programming
features or options must be limited to specific values or not used at all as
indicated below.