A-108
PFC-6030 • 5403595 • REV C-1 • 10/13
Appendix A: Basic Operating Instructions
These instructions must be framed and displayed next to the PFC-6030 panel in accordance with NFPA 72 fire code for Local
Protected Fire Alarm Systems. Test the system in accordance to NFPA 72.
Table 23: Button Functions
Button
Function
ACK
Arrows
Drill
Esc
Reset
Silence
Table 24: Operating Instructions
Operation
Task
Silence Alarms, Troubles
Press the
SILENCE
pushbutton.
Acknowledge Alarms,
Troubles
Press the
ACK
pushbutton.
Reset Alarms
Press the
RESET
pushbutton.
View Alarms, Troubles
Press
arrows
to view alarms / troubles.
Conduct a Fire Drill
Press the
DRILL
pushbutton
;
press the
RESET
button to exit Drill mode.
View Point’s Status
•y
Press
ENTER
to display the
Main Menu
.
•y
Press
5
–
System Tools
; enter
panel’s code
.
•y
Press
2
–
Point Control
.
•y
Scroll
Up/Down
to choose
Internal SLC
/
PWR
, and press
ENTER.
•y
Enter
Addr / Ckt No.
and press
ENTER
.
•y
Press
Up/Down
to view previous / next points.
Check Detector Sensitivity
•y
Press
ENTER
to display the
Main Menu
.
•y
Press
5
–
System Tools
; enter
panel’s code
.
•y
Press
1
–
SLC Tools
.
•y
Press
1
–
SLC Pinpoint
.
•y
Enter
Addr #
, press
ENTER
; detector address and type displays.
•y
Press
ENTER
to display current usage.
•y
Press
Up
to display
Day/Night Sensitivity settings
.
•y
Press
Up / Down
to scroll through point’s day / night sensitivity settings.