Automist Smartscan Hydra
®
DIOM Manual - version 3.01.0
Plumis Ltd Copyright © 2020. All Rights Reserved.
Page 98 of 116
S MA RT SC AN
®
Software update
process
IMPORTANT!
Updating the software is required as part of the maintenance of the system and can only be
performed by an Authorised Reseller Installer with a valid certificate. Switch off electricity at the mains
before working on existing circuits. Take care not to touch the PCB. Do not over tighten the terminals.
The latest version of the software is uploaded to the datalogger once a year by Plumis.
Locate the controller within the customer’s house. Common locations include near the RCD. Check that only
the controller green LED is lit, showing the controller is powered with no errors. Unscrew fastening screw(s)
with a small Philips head screwdriver. Be careful with the screws as you will need them when reassembling.
Expose the controller PCB by lifting the lid up and to the side. Be careful not to lift too far up as the flexible
keypad is connected to the PCB.
The PCB has three areas of interest on the board:
a)
Software LED. This will be illuminated and flickering when software is running on the board.
b)
Power LED to indicate the board is powered.
c)
6pin needle programming port. We will be connecting to this to reprogram.
Figure 89: Inside the controller
Setup the Kit
Remove the Flasher and 6pin needle adapter from the kit box. Insert the 6pin needle adapter into the
Flasher. Turn on the Flasher by pressing the power button, it will now display "Ready".