Mechanical Specification:
•
2-piece filter (head and jar), complete with cartridge
•
80
μm
mesh, less than 0.8 times the area of the smallest orifice in the system
•
Head: reinforced polypropylene.
•
Vase: transparent SAN.
•
O-ring: EPDM.
•
Cartridge: washable. Filtering net Polyester.
•
Applications: filtration of sand, scales, silt, fine material.
Pump
The Automist
pump should be:
a)
located such that it is unlikely to be affected by a fire;
b)
located where the temperature can be maintained above 4 °C;
c)
protected electrically by suitable fusing;
d)
protected against the effects of fire; and
e)
suitably protected against corrosion
To mitigate overheating when running for long periods, the pump must be installed in one of the following
locations with clearance of 100 mm at front and rear:
•
In a room or cupboard with a volume of at least 0.124m
3
, that is separated by a fire resisting
partition from the mist-protected room(s) that it serves. Alternatively, a flame proof enclosure
(G0001_M) can be purchased from Plumis for the purpose of protection, to minimise the effect of a
fire to the pump when it is in the room it is trying to protect.
•
In a cupboard with a volume of at least 0.124m
3
, within a room that the pump serves, with the top
of the pump less than 80cm above finished floor level.
Additional clearance at the front and the rear of the pump must also be provided to accommodate the
connections.
Automist Pump Specification:
Weight
7 kg
Size
365 mm (height) x 240 mm (depth) x 181 mm (width)
IP Rating
IP24D
Pump Unit
Operating Pressure
80 – 110 bar
Flow rate
6 litres per minute
Rated Speed
3460 rpm
Inlet Pressure (Static)
1 – 6 bar
Pression Spike
125 – 135 bar
Input Voltage
(Class I system protective earth)
230VAC ±10% 50Hz
Input Current
Pumping Mode
1.7kW, 8A maximum
Scanning Mode
30W, 0.5A maximum
Idle Mode
2W maximum
Cold Start Inrush
45A
Output Voltage
IN port (controller)
24VDC ±2.5%
OUT port (sprayheads)
24VDC ±2.5%
Output Current
IN port (controller)
1.1A maximum current limited
OUT port (controller)
1.1A maximum current limited