Automist Smartscan Hydra
®
DIOM Manual - version 3.01.0
Plumis Ltd Copyright © 2020. All Rights Reserved.
Page 55 of 116
S MA RT SC AN
®
Figure 47
:
Correct trunking installation with double
elbows
Figure 48
:
At risk trunking installation with hose
bending
Install the two elbows to the inlet port of sprayhead in the orientation that the 180-degree bend is pointing
to the back side of the sprayhead. Tighten the two connections with a wrench. Connect the hose inside the
trunking to the sprayhead and tighten the connection with a wrench. Install the sprayhead to the trunking
and gently guide the slack of hose inside the trunking.
It can be useful to house the pump and filter behind a fireproof enclosure which is fastened to the wall to
prevent the occupant from tampering with the pump and water inlet. The volume of the enclosure must be
at least 0.124m
3
to prevent overheating.
Any pump enclosures and trunking should be made from materials specially designed for sprinkler boxing,
for example:
FR sprinkler boxings (FRSB) is suitable for use in internal dry conditions as defined in EN622 part 5.
Materials of this type are suitable for use in Hazard Class 1 of EN 335-3. In addition to being manufactured
from FSC® certified 12 mm thick moisture resistant MDF board the material used in our flame retardant
sprinkler boxings is also compliant with Euroclass B standards. The range of dedicated accessories available
for FRSB products are also manufactured from the same Euroclass B compliant material. All paint coatings
used on FRSB products are coated with flame retardant BS EN Class B s1 d0 paint.