Compatible detectors/alarms
IMPORTANT!
Always follow the manufacturer’s instructions when installing wired detectors. A 24-volt wired
connection must be made between the detector and the sprayhead location using fire protected cable.
ONLY the following wired detectors are compatible with the Automist system:
Apollo Orbis
•
Apollo Orbis ORB-OH-13001-APO Multisensor detector.
•
Apollo 65 Series A1R (Only Heat).
https://www.safelincs.co.uk/apollo-series-65-a1r-heat-detector/
An Apollo heat detector should only be chosen over and above a multisensory detector if it is not possible
to use a multisensor detector as the type of substance encounter causes frequent false alarms. Use of
heat detectors for code compliance should be verified with Plumis as this type of alarm is slower to react
than multisensory detectors.
ONLY the following wired detector bases are compatible with the Automist system:
•
Apollo Orbis TimeSaver Base ORB-MB-00001-APO.
https://www.apollo-fire.co.uk/products/range/orbis/mounting-bases/orb-mb-00001-apo-orbis-
timesaver-base-with-continuity-switch
•
Apollo Orbis TimeSaver LX Base ORB-MB-00002-APO.
https://www.apollo-fire.co.uk/products/range/orbis/mounting-bases/orb-mb-00002-apo-orbis-
timesaver-base-lx-without-continuity-switch
The options below should ONLY be used when integrating with other alarm systems (see page 50):
AICO
•
Ei3024 Multi-Sensor Fire Alarm (kitchen only)
https://www.aico.co.uk/product/ei3024-multi-sensor-fire-alarm/
•
Ei3016 Optical Smoke Alarm
https://www.aico.co.uk/product/ei3016-optical-smoke-alarm/
The following relay base is compatible with Automist, because it monitors the detector status and has an in-
built battery backup in case of power loss:
•
The Ei414 Fire/Co Alarm Interface provides either a wireless interface via RF between a Radio Link,
Ra and SmartLINK Alarm systems. As well as a physical (hard-wired) interface via a link
cable between Warden Call/ Telecare systems. The Warden Call System in turn is programmed to
perform the desired function, on receipt of these signals. The Ei414 Fire / CO Alarm Interface can
be used to connect Ei Electronics RadioLINK Alarm Systems to suitable other Systems such as Fire
Panels, Telecare Systems, Auto Diallers, Security Systems etc. The Ei414 has 3 output relays for Fire,
CO & Service that can be triggered by an Ei Electronics RF Alarm System. These relays can be
directly connected to Automist. The Ei414 must be House Coded to the other RadioLINK devices in
the system.
https://www.aico.co.uk/downloads/ei414-instructions