S MA RT SC AN
®
Figure 27: Preferred position
alongside a light switch
Figure 28: Preferred position
alongside a recessed shelf
Figure 29: Preferred position
behind a sink
On longer walls and hallways, two sprayheads (less than 4m apart) can be used to cover each other. Each
sprayhead accommodates for a potential obstruction to the next one.
Figure 30: Utilising one sprayhead proximity to another
Finally, consideration should be taken to not position heads too close to corners. If the head is too close to
a corner (<0.55m) it can be obstructed by movable furniture on the adjacent wall.
Figure 27: Preferred position >0.55m from adjacent wall
IMPORTANT!
Authorised Reseller Installers (Designer and Commissioners) can deviate from the layout plan
if they can justify the principles are being satisfied but should update the drawing so a true representation
of what was installed is captured, with the rationale.
DO NOT
PLACE
0.55m
IDEAL
0.95m