Automist Smartscan Hydra
®
DIOM Manual - version 3.01.0
Plumis Ltd Copyright © 2020. All Rights Reserved.
Page 77 of 116
S MA RT SC AN
®
Commissioning Procedure
Commissioning incorporates a leakage test, a function test, and an alarm test (see page 86) by replicating a
full response to fire. It should only take place when the system is in its ‘ready for service’ state. A manual
commissioning form (printable A4 2 pager) from the Partner Site must be used to capture all the key
information about your installation (see APPENDIX H on page 109). This record can be used to input the
information into the digital commissioning form online.
Uncommissioned state
- Press and hold the TEST and ENTER buttons for 10 seconds to enter
commissioning mode. You can only enter commissioning mode within 60 mins of system
power on, this is to avoid unwanted uncommissioning.
Figure 71: Uncommissioned state
1.
Commissioning address state
– The single flash of the GREEN LED on the controller indicates
commission process one. The number of flashes of the YELLOW LED on the controller
indicates the number of addressed heads. Press the sprayheads to pair and unpair them, a
pulsing yellow sprayhead is unaddressed, and a solid green head is addressed. Long press
TEST for 10 seconds to clear the commissioning, if required. Press ENTER on the controller to
go to the next stage. Short hold STOP to go back to the previous state, if required.
YELLOW LED solid