Automist Smartscan Hydra
®
DIOM Manual - version 3.01.0
Plumis Ltd Copyright © 2020. All Rights Reserved.
Page 79 of 116
S MA RT SC AN
®
Note
: When pairing sprayheads to multiple wired alarm in series, only the alarm at the end of
the series must be triggered at alarm commissioning state. But the rest of the alarm(s) in this
series must be tested with “Alarm Test Mode” after commissioning.
Figure 74: Commissioning mode – commissioning alarm state
Figure 75: Gently press the outside surface of the sprayhead with your finger to pair it
3.
Commissioning flow state
– Three flashes of the GREEN LED on the controller indicates
commission process three.
IMPORTANT!
Always select the lowest sprayhead and nearest to the pump first for flow
testing first before progressively moving higher and further away from the pump. This takes
into consideration the most effective way to drain the hoses.
IMPORTANT!
During the flow test and draining process, a small amount of water will possibly
come out of the drain hole on top of the sprayhead’s main body block (drain hole not visible as
GREEN LED flashing
twice, YELLOW LED
flashing the number
of heads paired to
the selected alarm
2
Heads remain yellow
pending alarm
selection. Once an
alarm is triggered,
unpaired heads turn
red, and paired heads
flash green the
number of paired
heads to the selected
alarm. Gently press
the head to
pair/unpair it.