Figure 63: Sprayhead water path connection
Position the pump unit as closely as possible to the mains water supply pipes. Open the front panel and
connect the wiring to the terminals as per the drawing (see page 60). The large gland near the top of the
unit is used to supply the power.
IMPORTANT
! Tighten the cable strain relief glands to ensure that any movement of the cable does not
result in movement or tension at the terminal block. Do not over tighten the terminals. Use a torque
screwdriver on the following setting: minimum 0.5Nm, maximum 0.6Nm. (Note: the green connector block
has Phoenix Contact SMKDSN 1, 5/ 5-5, 08).
Once you have successfully connected the controller to the pump, connect the pump to the first sprayhead
and to the mains. Once you have finished with the wiring close the front panel, now you are ready to test
the first head.
IMPORTANT!
Always
hold the pivot base
whilst tightening the
high-pressure hose
Pivot base