E) Commissioning
The Automist Smartscan Hydra Controls
Figure 69 : The Automist Controller
STOP Button: Pressing the STOP button during a fire condition will stop the Automist Smartscan Hydra pump for 2
minutes. After activation, the system will alarm for 12 minutes. During this time if at the end of the first 2 minutes
(during the last 10 minutes), an alarm triggers the system will reactivate. This mode was created to address the
fire returning in the 12 minutes after the occupant believes it has been extinguished. During this time do not
switch off the power or it will reset the 12-minute timer. If the alarm condition has ended, Automist Smartscan
Hydra will return to an uncommissioned state (solid YELLOW LED on) and requires service.
The customer must
contact the Authorised Installer after an activation (see page 92).
In error conditions, pressing the STOP button temporarily silences the error sounds for 12 hours.
In the SYSTEM OK stand-by, pressing and holding the TEST button may be used to enter ALARM TEST MODE. The
YELLOW LED will then start flashing – this indicates that ALARM TEST MODE is activated. In this mode you have 15
minutes to press the test button on a wireless alarm, or trigger a wired alarm with heat or smoke, causing the
heads paired to said alarm to begin scanning (2 scans will be performed) and flashing red and yellow. ALARM
TEST MODE is deactivated by pushing the ENTER or STOP button; this will be confirmed by the GREEN LED
returning to constantly lit. Testing the alarms outside of this mode by pushing the button on the wireless alarm
will make it beep and the Automist system will do nothing.