background image

 

 

PCL

 

 

 

Pleiger Elektronik GmbH & Co. KG 
www.pleigerelektronik.de 
Fon +49 2324 398 333 

17

 / 

65

 

 

Pleiger Control Loop 

Manual version 2018-03    

 

Bus IO Unit (PCL-IO) 

The PCL-IO is used to acquire 
digital and analog data via the 
PCL system. Additionally con-
trol commands can be sent to 
the process by means of two 
relays. The PCL-IO provides 
the same bus interface like the 
PCL-VCI. All safety features of 
the PCL are also implemented. 
The PCL-IO is encased into a 
waterproof (up to IP68) casing. 
Water tight cable fittings are 
used for the complete cabling.   

6.1  Analog / digital in-

puts 

The PCL-IO provides 8 analog inputs with an input range of 0..20,4mA. The internal resistance of 
each input is 100Ohm. The inputs are not isolated from one another and therefore only suited for float-
ing current sources like pressure or temperature sensors. The PCL-IO also provides 24VDC to supply 
the sensors. Self-resetting fuses protect the inputs against overload due to short circuit in the sensor 
cabling.  

An 8-fold switch on the board is used to configure the input either as analog or digital. If an input is 
used as digital input a 24V input signal is converted to a 4mA current. Please note that these input 
must only be used for floating signal sources like liquid level switches, relays etc. 

      current input = switch position ON 
      digital input   = switch position OFF 

CAUTION 

 

Malfunction / Damage 

Take care that the DIP-Switches are o

nly in “ON”-Position, if the equivalent input is 

used with an analog 4-

20mA signal! The delivery state is “OFF”! 

6.2  Isolated digital inputs 

Additionally each PCL-IO provides two opto-isolated inputs. Both inputs have common 0V. 

6.3  Digital relay outputs  

For control purposes each PCL-IO is equipped with two relay outputs. Both contacts of a normally 
open relay are connected to separate terminals. 

6.4  Technical data PCL-IO 

Power supply AC 

230V 

20%, 45…65Hz 

max. power loop current 

16A

rms

 

current to detect a short circuit 

<= 10 mA 

Power consumption 

max. 6W 

Power supply for ext. sensors 

24VDC 

0,7V, max. 200mA 

Max error of analog inputs 

max. ±0,4% of full range 

Trigger level of digital inputs  

12V ±2V 

Ambient temperature (casing) 

-25°C ... 55°C 

Figure 6-1: PCL-IO-card 

Summary of Contents for PMC 2000

Page 1: ...en Im Hammertal 51 Fax 49 2324 398 389 www pleiger elektronik de info pleiger elektronik de PCL PCL Modules Pleiger Control Loop Manual version 2018 03 subject to modification System Description PCL V...

Page 2: ...plies 9 4 4 4 Installation rules 9 4 5 Fusing 10 5 Valve Control Interface PCL VCI 11 5 1 Interface to actuator 11 5 1 1 Quick Closing Operation 11 5 2 Valve Control Function 12 5 2 1 PCL VCI versions...

Page 3: ...rive 34 10 2 7 Backup operation for an EHS with continuous drive 35 10 2 8 Failure indication 36 10 3 Advanced operation with analyzing function 38 10 3 1 PLC node 40 10 3 2 PLC VCI node for an EHS 41...

Page 4: ...struction in this manual and the available imprint on the component 1 3 Intervention into the component If malfunctions occur or something is dubious please contact the manufacturer Intervention into...

Page 5: ...nents meet the requirements of the following Directives DNV GL Class Guideline DNVGL CG 0339 Nov 2016 The following approvals apply Type approval TAA00001FM by DNV GL Type approval TAA00000S3 by DNV G...

Page 6: ...and other parts of the system Even in most cases of severe damage not more than two drives of the system will fail The main components of the PCL System are Redundant hot standby busmaster PCL Master...

Page 7: ...an be selected by several parame ters Each data loop can serve up to 100 nodes and up to 250 nodes may be connected to a busmas ter resp a pair of busmasters If more than 60 nodes shall be connected t...

Page 8: ...ecking The node address in the range 1 to 250 is simply set by means of an 8 bit DIP switch This is a very simple technique and does not require special skills or equipment during installation or when...

Page 9: ...ail Because the PCL masters supervise the power loop voltage this event is going to be indicated via Modbus connec tion immediately The fuse may now be reset manually Of course without any additional...

Page 10: ...rs power loop Resistance Length 1 3x1 5 mm 9 08 mOhm m 176 m 2 2x2 5mm 7 26 mOhm m 220 m 3 4x1 5mm 6 05 mOhm m 264 m 4 3x2 5mm 5 45 mOhm m 294 m 5 2x4mm 4 54 mOhm m 352 6 4x2 5mm 3 63 mOhm m 441 m Tab...

Page 11: ...er hull of the cable is damaged the cable must be replaced This holds true even if the damage is diminutive 4 5 Fusing Each power bus loop must be fused separately with two 16A automatic fuses with B...

Page 12: ...ely hard wired quick close system If the external supply voltage is turned off the valve will close in any case 5 1 1 Quick Closing Operation The PCL system uses two different ways to connect the driv...

Page 13: ...arated hydraulic unit requires additional relay QC_SCQ single acting valve with separated hydraulic unit requires additional relay external coil supply for quick closing function required EHS_DEx doub...

Page 14: ...d switch 8 sets the most significant bit of the address See also chapter 3 3 2 Data communication and address selection and 5 5 5 Connector extended inputs and outputs for further information This boa...

Page 15: ...supply quick close Table 5 3 PCL VCI card EHS connector 5 5 PCL VCI with extended inputs and outputs V3 3 and V3 4 vertical connectors The extended version of the VCI provides some extra features Mos...

Page 16: ...to remote mode standard 1 There is a local release command that can be send from the SCADA system or any PLD 2 By pressing both buttons open close simultaneously for 2 seconds Returning to remote mode...

Page 17: ...signals for the SCADA system 5 5 4 Technical data extended inputs and outputs Analog Inputs input range 0 20mA input resistor 100 Ohm resolution 12 Bit precision max 0 4 of measuring range typ 0 2 Dig...

Page 18: ...ling An 8 fold switch on the board is used to configure the input either as analog or digital If an input is used as digital input a 24V input signal is converted to a 4mA current Please note that the...

Page 19: ...pply Please note that each node will turn the phase of the power bus by 180 See chapter 7 PCL Power Control PCL PC for details 6 4 2 Connector for process IO Pin I O Meaning 1 in analog digital input...

Page 20: ...and begin of power loop Figure 7 1 Connection of a PCL PC module the Busmaster and the first two nodes in the PCL Loop 7 2 Technical description PCL PC Pin layout PCL PC Version 9321209840 Pin I O Mea...

Page 21: ...the module on the B side depends on the No of nodes in the power loop It has to be connected as stated below in Figure 7 2 if the number of PCL nodes in that power loop is odd as stated in Figure 7 3...

Page 22: ...side 5 6 Power bus L2 B side 1 2 7 8 Power bus L1 B side 3 4 11 9 Data bus A side 12 10 Data bus A side 11 Data bus B side 9 12 Data bus B side 10 Table 8 1 Connection table of PCL BC modules NOTICE...

Page 23: ...5 interface used to connect a supervisory control system SCADA via Modbus RTU as Modbus RTU slave Processor board mc3 with 32 bit processor USB service interface 100Mbit s Ethernet port isolated CAN i...

Page 24: ...uit Flashing CAN sending data 4 LED Green ON CAN bus not connected open OFF CAN bus off short circuit Flashing CAN receiving data Table 9 2 Busmaster Status LEDs from top to bottom Ethernet LAN port u...

Page 25: ...us RTU Interface The RS 485 port of the dc power supply module is intended to connect a supervisory control system via Modbus RTU The acts as a RTU slave whereas the SCADA system is the master The bau...

Page 26: ...ient temperature 25 C 55 C Digital inputs dea8 threshold level 12V 4V max input voltage 72V Digital outputs dea8 max contact voltage 72V max contact current 1A Serial interfaces Sub D 9 pin to PCL dat...

Page 27: ...o 8 pair of busmaster One busmaster can serve up to 250 valves and or I O cards Each busmaster can control up to 8 data loops One data loop can contain up to 100 valves Each data loop can be equipped...

Page 28: ...f the firmware is shown for service act This example has 2 busmas ter and the place for 6 additional busmasters The valve systems are listed in the process picture The example contains 9 valve systems...

Page 29: ...th analyzing function The user wants to inspect a failure in the system It is necessary that the user has sufficient knowledge about the PCL System with data loop and power loop 10 2Backup operation I...

Page 30: ...a system has more than 48 nodes Further 16 nodes instead of the first 16 nodes are shown after pressing the button Now there is also a button available The state of the valves is shown in the list For...

Page 31: ...2018 03 Figure 10 6 PCL VCI node EHS open close page in observing mode The name of the valve and the system is shown Additionally there is an optional description In this example the description expl...

Page 32: ...There is no backup operation for the IO available You can see the digital inputs and the digital out puts The analog inputs are pointed in the scale of 0 to 20 48 milliamps 10 2 3 PLC VCI node for an...

Page 33: ...igure 10 11 PCL VCI extended In and Outputs detail view The inputs are always pointed as analogue raw value in the scale of 0 to 4096 The function of each input and output can be parametrized The poss...

Page 34: ...trol permission for backup operation For getting the control permission you have to press get A decimal keyboard will appear and you have to enter the PIN 1234 Figure 10 12 PCL VCI node EHS open close...

Page 35: ...ction of LC The function to block the valve is not available in the backup operation This function is reserved for the advanced operation Figure 10 13 PCL VCI node EHS open close page in operation mod...

Page 36: ...35 65 Pleiger Control Loop Manual version 2018 03 10 2 7 Backup operation for an EHS with continuous drive Figure 10 15 PCL VCI node EHS continuous drive page in operation mode with local control acti...

Page 37: ...busmaster is defect there is no current information about this node available Figure 10 17 Node page if no connection to a busmaster is available Failure of PCL system and failure of the actuator are...

Page 38: ...ain switch board and the emergency switch board are powerless and the PLD and the bus master and the data loop and the power loop are powered by a UPS then the UPS indication is high lighted In this c...

Page 39: ...nalyzing function Initial condition is the startup picture Figure 10 18 Systems overview page The picture of the state of the busmaster pair is shown after selection of the busmaster Example BM1 Figur...

Page 40: ...oop belonging to the color is described at the bottom of the picture The number 0 indicates that there is no power loop used There is space for 48 nodes in the picture The button Next is available if...

Page 41: ...he node OF Selection of the node name will change into the picture of the advanced operation with analyzing func tion There is no selection of a node available when the connection to the busmaster is...

Page 42: ...arameters All parameters are pointed and the grey colored parameters can be changed By pressing back you return to the list of the nodes of the data loop 10 3 3 PLC IO Figure 10 24 PCL IO node page in...

Page 43: ...ly A decimal keyboard will appear and you have to enter the PIN for parameter control permission Figure 10 25 PCL VCI node page with parameters and permission to change them You can end the permission...

Page 44: ...blocked Neither the SCADA System nor the PLD can control the valve 10 3 7 End the blocked state of a valve After pressing BL by a blocked valve a decimal keyboard will appear and you have to enter th...

Page 45: ...ith separated hydraulic unit requires additional relay external coil supply for quick closing function required EHS_DEx double acting valve for use in hazardous area requires additional CM ExE module...

Page 46: ...lose fnct 0 0 close on communication loss 0 11 QC_SO EHS_SO w inverted output 0 0 open on communication loss 0 12 EHS_SCH spring close hydraulic override 0 0 close on communication loss 0 13 PCL_IO 14...

Page 47: ...lektronik de Fon 49 2324 398 333 46 65 Pleiger Control Loop Manual version 2018 03 10 3 10 Modify the parameter runtime The runtime of the valve from leaving close position until open position is reac...

Page 48: ...tuator can be parametrize to one or more up to four quick close circuits Figure 10 31 Quick Close parameter editor page Value of the parameter Input Quick Close 4 Input Quick Close 3 Input Quick Close...

Page 49: ...ections of the busmaster the picture is divided into three rows Connection to PLD Connection to SCADA system Connection to data loops 10 4 1 Symbol explanation for the connection to SCADA system The c...

Page 50: ...n correlates with the active connection to the SCADA system The SCADA system selects the active connection between busmaster A and B The busmasters A and B only have to select the request if the SCADA...

Page 51: ...eigerelektronik de Fon 49 2324 398 333 50 65 Pleiger Control Loop Manual version 2018 03 Figure 10 36 The PLD has no connection to busmaster B and the CAN bus connection is de fect Figure 10 37 The PL...

Page 52: ...ects the data loops if it doesn t get commands for the nodes No command is available neither from the SCADA system nor via CAN bus Table 10 4 Symbolization of the PCL bus state These informations are...

Page 53: ...omatic functions like heeling bilge operation won t be longer available Digital outputs on PCL VCI and PCL IO can be still controlled by the SCADA system If the input is true the area is colored green...

Page 54: ...Break power loop on one side 3 30s checking connection to nodes power loop test 4 If an error was detected the selftest procedure will be stopped at that point 5 Close power loop again stop polling da...

Page 55: ...bance in the loops is not yet repaired as result of the last selftest or one busmaster cannot fetch all his dedicated nodes How to start a selftest 1 Press 2 A decimal keyboard will appear and you hav...

Page 56: ...t be reached by the tested busmaster is marked as offline on the data loop page The cause of the disturbance may be the first offline node the last node before from direction of the tested busmaster o...

Page 57: ...errors that were found during a selftest First offline node from direction of the tested busmaster A Master A polls the nodes begin ning with the lowest number in the data loop here no 1 Failure detec...

Page 58: ...th system failure Possible indications of failure File Sys Failure Failure in the busmaster internal file system detected INI File Failure Plausibility check failure of Master ini file detected PCL Fi...

Page 59: ...uration and service functions These functions are primarily made for service personal but you should also know about them Initial condition is the startup picture Figure 10 42 Systems overview page Se...

Page 60: ...page Here you can set the brightness for the display and save it for further use It can t be set to a non usable value You can do it as it s affordable to the ambient light You don t need a permission...

Page 61: ...nual version 2018 03 Figure 10 46 PLD configuration and service page Pressing the second button will change into the update picture Figure 10 47 Update page If it is necessary to update files from PLD...

Page 62: ...49 2324 398 333 61 65 Pleiger Control Loop Manual version 2018 03 You can update each busmaster after you got the permission PIN for update Figure 10 48 Update page with right permission But you have...

Page 63: ...ient temperature 0 C 55 C Environmental protection category IP54 frontside Ethernet interface RJ45 100 Mbps full duplex Modbus TCP protocol Serial Interface RS485 2 x 38 4 kBaud project specific USB I...

Page 64: ...re 10 4 Systems overview page 28 Figure 10 5 Node list of one system 29 Figure 10 6 PCL VCI node EHS open close page in observing mode 30 Figure 10 7 PCL IO node 31 Figure 10 8 PCL VCI node EHS contin...

Page 65: ...9 Figure 10 34 PLD with selected connection to one busmaster and passive to the other 49 Figure 10 35 The PLD has no connection to busmaster B and the CAN bus connection is defect There is no informat...

Page 66: ...able 6 2 PCL Bus connection table PCL VCI card 18 Table 6 3 PCL IO card process signal connector 18 Table 7 1 PCL PC connector 19 Table 8 1 Connection table of PCL BC modules 21 Table 9 1 BusMaster da...

Reviews: