PCL
Pleiger Elektronik GmbH & Co. KG
www.pleigerelektronik.de
Fon +49 2324 398 333
10
/
65
Pleiger Control Loop
Manual version 2018-03
Both ends of the bus loop or of a power loop should be laid in separate paths to avoid a damage of
both ends at the same time. If the outer hull of the cable is damaged the cable must be replaced. This
holds true even if the damage is diminutive.
4.5 Fusing
Each power bus loop must be fused separately with two 16A automatic fuses with B characteristic.
Attention:
Fuses with different characteristic or different design current must not be used!
CAUTION
Material damage
Wrong system design, wrong installation, incorrectly connected drives or defective ca-
bles may cause damage to the PCL-System-Components!