Pleiger Control Loop
Manual version 2018-03
•
Up to two digital outputs can be controlled by the SCADA system in the same way. If the equivalent
bit in the register is set, the output on the VCI card will be set until the bit in the register is reset
again. Depending on the parameters the outputs can be also set to 0 if the communication from the
VCI to the busmaster(s) fails for more than 5s!
NOTICE
Combinations and parameters for extended inputs and outputs
Not every combination of functions of inputs and outputs can be realized!
For example, one key switch and one button can’t be combined to be used as local
control unit but, as another example, it is possible to use both ouputs for local indica-
tion and both inputs to collect digital or analog sensor signals for the SCADA-system.
5.5.4 Technical data (extended inputs and outputs)
Analog Inputs
input range
0
…20mA
input resistor
100 Ohm
resolution
12 Bit
precision
max ±0,4% of measuring range, typ. ±0,2%
Digital Inputs
threshold
9
…12VDC
max. input current
5mA
Digital Outputs
PNP type, max. 50mA each, no short circuit protection
Operating Temperature
-25°C ... 55°C
Table 5-4: PCL-VCI v3: technical data of extended in- and outputs
5.5.5 Connector (extended inputs and outputs)
Pin I/O
Meaning
Local Control Function
1
in
input 1
, 0…20mA or +24V
Mimic Close Input
2
24V
supply voltage 19…22VDC
3
in
input 2
Mimic Open Input
4
24V
supply voltage 19…22VDC
5
out
PNP output max. 20mA
Feedback Close Out (0V = Close)
6
out
PNP output max. 20mA
Feedback Open Out (0V = Open)
Table 5-5: Connector PCL-VCI v3 extended in- and outputs
CAUTION
Malfunction / Damage
Take care that the DIP-
Switches 9 & 10 are only in “ON”-Position, if the equivalent in-
put is used with an analog 4-20mA signal! In case of external switches or digital sensor
signals, the switch has to be “OFF” (factory setting)!