Use, maintenance and warning instructions
HIGH PRESSURE REGULATOR
|
COMMISSIONING
|
REV. 00
8.9 - CALIBRATION OF THE PRESSURE SWITCH FOR LINE OFF 2.0
NOTICE!
For the pressure switch calibration procedure, refer to paragraph 8.8.3 “Calibration procedure for pressure
switches 102M/102MH - 105M/105MH”.
8.10 - DEVICE CALIBRATION
8.10.1 - CALIBRATION OF 200/A SERIES PILOTS
10
Fig. 8.30.
200/A series pilots
Turn the adjusting screw (10):
• anti-clockwise to decrease the adjusted pressure;
• clockwise to increase the adjusted pressure.