76
ASX 176
EN
Use, maintenance and warning instructions
HIGH PRESSURE REGULATOR
|
INSTALLATION
|
REV. 00
To prevent the pneumatic connections of the sensing lines from collecting impurities and condensation, it is necessary
that:
• the pneumatic connection couplings are always welded on the upper part or at maximum 90 degrees on the axis of
the piping (refer to fig. 6.22);
• the hole in the piping has no burrs or internal protrusions;
• the slope of the pneumatic connection is always 5-10% towards the downstream pipe connection.
Fig. 6.22.
Welded connections of the pneumatic connection