The IP address and the subnet mask must be checked and modified if necessary.
–
The update time for inputs should be set to “512 ms” (default).
–
The update time for outputs should be set to “512 ms” (default).
–
The monitoring time should be set to “2000 ms” (default).
–
The interface modules must be selected from the module catalog and added to the sta-
tion.
Figure 9-3
Device details with modified settings
The PROFINET variables can then be created and used in the control program.
In addition to the “PNIO_DATA_STATE” standard variable, the switch provides the link sta-
tus as a process data byte for each port. If the “PNIO_DATA_VALID” bit for the “PNIO_-
DATA_STATE” variable declares the switch process data as valid, the process data item for
a port can have the following values (see Section “Additional process data” on page 161):
–
Value = 1 - Active link
–
Value = 2 - No active link
–
Value = 3 - Link present, but partner cannot establish link (only for FX ports - Far End
Fault Detection)
–
Value = 4 - Port is administratively disabled
–
Value = 129 - Port is active, but in the “Blocking” state due to the redundancy protocol
(RSTP, MRP)
Process data can only be accessed if the parameterized desired configuration on device
startup corresponds to the actual configuration.
The “Status” word and the “Control” word of the management agent are not used.
9.2.3
Configuration via the engineering tool
The universal parameter editor (UPE) can be used to configure the switch via the engineer-
ing tool (PC Worx).
–
Activation/deactivation of PROFINET alarms
–
Configuration of port mode
–
Configuration of port state
Summary of Contents for 2700290
Page 1: ...User manual Smart Managed Narrow Switch Order No ...
Page 8: ...FL SWITCH SMN 6 PHOENIX CONTACT 8089_en_03 ...
Page 24: ...Smart Managed Compact Switch 24 PHOENIX CONTACT 8089_en_03 ...
Page 42: ...Smart Managed Compact Switch 42 PHOENIX CONTACT 8089_en_03 Figure 4 24 Diagnostics web page ...
Page 108: ...Smart Managed Compact Switch 132 PHOENIX CONTACT 8089_en_03 ...
Page 114: ...Smart Managed Compact Switch 138 PHOENIX CONTACT 8089_en_03 ...
Page 148: ...Smart Managed Compact Switch 172 PHOENIX CONTACT 8089_en_03 ...
Page 150: ...Smart Managed Compact Switch 178 PHOENIX CONTACT 8089_en_03 ...