For Type A signs there is a special diagnostic channel which can help when checking sign communication.
It is channel “0A” (the channel right after channel 9). If you set your sign to this channel you will see a
single digit number scroll across the screen. The digit will change every second if there is communication
to the sign. If you see any of the following on the screen it means there is no communication at present:
Same number not changing.
Blank.
The “Take next battery ...” message.
Note: this feature is present in version 4.15 and higher.
Troubleshooting a Type A iBOS
®
display
1.
Trace phone cord from “faulty” Scrolling Display to the 5 Port Phone Jack inside the iBOS
®
Control
Box and move cord to another jack to verify if signal can be received by the Display from another
connection.
2. Inspect the phone cord connecting the Control Box to Display that you are troubleshooting.
a. Is the phone cord no longer than 25
’ (7.6 m)?
b. Is it a Cross-Over Cable? NON-CROSS-OVER CABLE = When looking at the clear phone
connector with the tab facing down and the phone cord coming to you, is the order of the
colored wire the same on both ends? BLACK, RED, GREEN, YELLOW. If one end is
Black, Red, Green, Yellow and the other is Yellow, Green, Red, and Black this is a CROSS-
OVER Cable and will not work with the Scrolling Display.
3. Verify that the display is assigned to the correct pool. The pool 1 display would need to be set as
ID01. Turn off the power to all the displays except the one you are programming.
c. Press ESC (display shows Ed Rn Del Set)
d. Press S (for set).
e. Press Enter. Continue to press until you see the ID number displayed.
f. Press
and
to change ID number. Use 1 for pool 1.
g. Press Enter until you see Ed Rn Del Set
h. Press R
i. Press P
j. Press A
RJ11 Wire
RJ45
Male Jack
(tab down)
Black
Red
Green
Yellow