1
4
.TROUBLESHOOTING
25 Expansion valve C
(liquid) pipe sensor
fault
1. The wiring of the sensor for the
expansion valve C (liquid pipe) is
connected loosely;
2. The sensor of the expansion
valve C
(
liquid pipe
)
fails;
3. The sampling circuit fails.
1. Reconnect the wiring of the
sensor for the expansion valve
C (liquid pipe).
2. Replace the sensor for the
expansion valve C (liquid pipe);
3. Replace the outdoor control
board.
26 Expansion valve D
(liquid) pipe sensor
fault
1.The wiring of the sensor for the
expansion valve D (liquid pipe) is
connected loosely;
2.The sensor of the expansion valve
D (liquid pipe) fails;
3.The sampling circuit fails.
1. Reconnect the wiring of the
sensor for the expansion valve
D (liquid pipe);
2. Replace the sensor for the
expansion valve D (liquid pipe);
3. Replace the outdoor control
board.
27
Expansion valve A
(gas pipe)
sensor
fault
1. The wiring of the sensor for the
expansion valve A (gas pipe) is
connected loosely;
2. The sensor of the expansion valve
A (gas pipe) fails;
3. The sampling circuit fails.
1. Reconnect the wiring of the
sensor for the expansion valve
A (gas pipe);
2. Replace the sensor for the
expansion valve A (gas pipe);
3. Replace the outdoor control
board.
28
Expansion valve B
(
gas pipe
)
sensor
fault
1. The wiring of the sensor for the
expansion valve B (gas pipe)
connect is connected loosely;
2. The sensor of the expansion valve
B (gas pipe) fails;
3. The sampling circuit fails.
1. Reconnect the wiring of the
sensor for the expansion valve
B (gas pipe);
2. Replace the sensor for the
expansion valve B (gas pipe);
3. Replace the outdoor control
board.
29
Expansion valve C
(gas pipe) sensor
fault
1. The wiring of the sensor for the
expansion valve B (gas pipe)
connect is connected loosely;
2. The sensor of the expansion valve
C (gas pipe) is fails;
3. The sampling circuit fails.
1. Reconnect the wiring of the
sensor for the expansion valve
B (gas pipe);
2. Replace the sensor for the
expansion valve C (gas pipe);
3. Replace the outdoor control
board.
30
Expansion valve D
(gas pipe) sensor
fault
1. The wiring of the sensor for the
expansion valve B (gas pipe) is
connected loosely;
2. The sensor of the expansion valve
D (gas pipe) fails;
3. The sampling circuit fails.
1. Reconnect the wiring of the
sensor for the expansion valve
B (gas pipe);
2. Replace the sensor for the
expansion valve D (gas pipe);
3. Replace the outdoor control
board.
45 IPM fault
There are many reasons for this
failure. You can check the driver
board fault LED to
further
analyze
the fault code of the drive board
and to learn about what leads to the
fault and how to operate it. Specific
information can be seen in table 5,
table 6.
See attached "analysis of the
driving board fault".
Fault
code
Fault
d
escription
Possible
r
eason
s
for
a
bnormality
How to
d
eal
w
ith
R
emarks
56
Summary of Contents for 3PAMSHHQC18-MZO2
Page 12: ...3 OUTLINES AND DIMENSIONS 3 Outlines and dimensions 18K Unit in mm 8...
Page 15: ...42K Unit in mm 3 OUTLINES AND DIMENSIONS 11...
Page 26: ...7 REFRIGERANT CYCLE 7 Refrigerant cycle 18K 24K 22...
Page 29: ...8 WIRING DIAGRAM 24K Electric wiring diagram 1993419 F 25...
Page 30: ...8 WIRING DIAGRAM 36K Electric wiring diagram 2000947 H 26...
Page 31: ...8 WIRING DIAGRAM 42K Electric wiring diagram 2087381 B 27...