1
4
. TROUBLESHOOTING
Table 4 Drive Fault Code (
24K/36K/42K
)
Fault
code
Fault description
Possible reasons for abnormality
How to deal with
1
Q axis current
detection, failure in
drive control
1. Compressor wire is not connected
properly;
2. Bad driver board components;
3. Compressor start load is too large;
4. Compressor demagnetization;
5. Compress or oil shortage serious
wear of crankshaft;
6. The compressor insulation fails.
1. Check compressor wire;
2. Change driver board ;
3. Turn on the machine after the
pressure is balanced again;
4. Change Compressor;
5. Change the Compressor;
6. Change the Compressor.
2
Phase current detection,
failure in drive control
1.Compressor voltage default phase;
2.Bad driver board components;
3.The compressor insulation fault.
1.Check compressor wire connection;
2.Change the driver board;
3. Change the Compressor.
3
Initialization, phase
current imbalance
Bad driver board components.
Change driver board .
4
Speed estimation,
failure in drive control
1.Bad driver board components;
2.Compressor shaft clamping;
3.The compressor insulation fails.
1.Change driver board ;
2.Change the Compressor ;
3.Change the Compressor .
5
IPM FO output fault
1. System overload or current
overload.
2. Driver board fails;
3. Compressor oil shortage,serious
wear of crankshaft;
4. The compressor insulation fault.
1.Check the air-conditioner system;
2.Change the driver board;
3.Change the Compressor;
4. Change the Compressor.
6
Communication
between driver board
and control board fault
1.Communication wire connect not
well;
2. Driver board fault;
3. Control board fault;
1. Check compressor wire connect.
2. Change the driver board;
3. Change the control board ;
7
AC voltage,overload
voltage
1. Supply voltage input is too high or
too low;
2. Driver board fails;
1.Check power supply;
2.Change the driver board;
8
DC voltage,overload
voltage
1. Supply voltage input is too high ;
2. Driver board fault;
1. Check power supply;
2. Change the driver board;
9
AC voltage imbalance
Driver board fails;
Change the driver board;
10
The PFC current
detection circuit fault
before compressor is
ON
Bad driver board components;
Change the driver board
11
AC voltage supply in
outrange
1.Power supply abnormal, power
frequency out of range;
2.Driver board fails;
1. Check the system;
2. Change the driver board;
12
Products of
single-phase PFC
over-current, FO
output low level
1. System overload, current is too large;
2. Driver board fault;
3. PFC fault.
1. Check the system;
2. Change the driver board;
3. Change PFC.
Inverter over current
(3-phase power supply
air conditioners)
1. System overload, current is too large;
2. Driver board fault;
3. Compressor oil shortage, serious
wear of crankshaft;
4. The compressor insulation fault.
1. Check the system;
2. Change the driver board;
3. Change the Compressor;
4. Change the Compressor.
13
Inverter over current
1. System overload, current is too large;
2. Driver board fault;
3. Compressor oil shortage,serious
wear of crankshaft;
4. The compressor insulation fault.
1. Check the system;
2. Change the driver board;
3. Change the Compressor;
4. Change the Compressor.
14
PFC over
current(single-phase
air-conditioner)
1. System overload, current is too large;
2. Driver board fault;
3. PFC fault.
1. Check the system;
2. Change the driver board;
3. Change PFC.
Phase imbalance or
phase lacks or the
instantaneous power
failure (only for
3-phase power supply
air conditioners)
1.3-Phase voltage imbalance;
2.The 3-phase power supply phase
lost;
3. Power supply wiring wrong;
4. Driver board fault.
1, Check the power supply;
2. Check the power supply;
3. Check the power supply wiring
connect;
4. Change the driver board.
15
The instantaneous
power off detection
1.The power supply is not stable ;
2.The instantaneous power failure ;
3.Driver board fault;
1. Check the power supply;
2. Not fault;
3. Change the driver board.
61
Summary of Contents for 3PAMSHHQC18-MZO2
Page 12: ...3 OUTLINES AND DIMENSIONS 3 Outlines and dimensions 18K Unit in mm 8...
Page 15: ...42K Unit in mm 3 OUTLINES AND DIMENSIONS 11...
Page 26: ...7 REFRIGERANT CYCLE 7 Refrigerant cycle 18K 24K 22...
Page 29: ...8 WIRING DIAGRAM 24K Electric wiring diagram 1993419 F 25...
Page 30: ...8 WIRING DIAGRAM 36K Electric wiring diagram 2000947 H 26...
Page 31: ...8 WIRING DIAGRAM 42K Electric wiring diagram 2087381 B 27...