b. Mode conflict
The operating mode of outdoor unit is decided by the operating mode of the indoor unit firstly
booted. Indoor unit subsequently booted will firstly determine whether it’s own mode is conflict
with the outdoor mode. If so, the indoor unit will automatically shut down after three beeps; If
there is no conflict, the indoor unit will boot normally. The relationship of mode conflict is as
follows:
Driven choice
Active mode
Cooling
Dehumidification
Heating
fan
Cooling
√
√
×
√
Dehumidification
√
√
×
√
Heating
×
×
√
×
Fan
√
√
×
√
√―――Mode conflict will not happen
×―――Mode conflict will happen
7) Outdoor four-way Valve Control
Four-way valve of the outdoor machine shuts down when cooling but starts when heating.
The operation of heating defrosting refers to defrosting operation and, when the heating remote
shutdown, the four-way valve disconnects in 50s when the compressor stops working.
8) Start-up Protection
To prevent compressor from restart frequently in the condition that system pressure has not been
completely balanced, it can’t be restarted within 3 minutes.
9) Pressure Protection
Pressure switch is normally kept open. When the pressure grows too high, the pressure switch
will close and soft will enter pressure protection control. soft will automatically decrease the
frequency. If the pressure is still unable to return to normal condition after decreasing frequency,
compressor will stop and report the fault code of pressure protection.
1
2
. CONTROL MODE
44
Summary of Contents for 3PAMSHHQC18-MZO2
Page 12: ...3 OUTLINES AND DIMENSIONS 3 Outlines and dimensions 18K Unit in mm 8...
Page 15: ...42K Unit in mm 3 OUTLINES AND DIMENSIONS 11...
Page 26: ...7 REFRIGERANT CYCLE 7 Refrigerant cycle 18K 24K 22...
Page 29: ...8 WIRING DIAGRAM 24K Electric wiring diagram 1993419 F 25...
Page 30: ...8 WIRING DIAGRAM 36K Electric wiring diagram 2000947 H 26...
Page 31: ...8 WIRING DIAGRAM 42K Electric wiring diagram 2087381 B 27...