Installation
Connecting the IDENTControl to ground
Screw the ground conductor to the housing with a crimp connector.
5.4.5
Ethernet connection guide
Network connection
Connect the network to the IDENTControl using a connector that conforms with AIDA. Two
sockets with the following pin assignment are located on the housing:
■
TD+
■
TD-
■
RD+
■
Not used
■
Not used
■
RD-
■
Not used
■
Not used
1
Housing
2
Serrated lock washer
3
Crimp connector
4
Lock screw
1
2
4
3
Caution!
The network socket is connected galvanically to the grounded housing. The Ethernet/IP
specification does NOT require the use of Ethernet cables with a shield connected to the RJ-45
plug at both ends.
However, we recommend using cables with a continuous shield only, in order to avoid EMC
issues.
Note!
Protection degree IP67
If you use only one of the two network connections, you must close the unused network port
with the blind plug ICZ-AIDA1-B to achieve the protection degree IP67. The blind plug ICZ-
AIDA1-B is available as an accessory.
See chapter 4.7.3.