4
Error/Alarms and
Troubleshooting
47
EN-RaychemHWATECOcontroller-IM-H57340 03/13
Error code
Definitions Cause/reasons
Remedy
Error 8:
Time is lost
Battery is drained due
to not being powered
for a long time.
Input time again (will be asked
by the unit when a button is
pressed)
Error 9:
Pipe temperature is
too low
(Only when temperature
alarm “yes” selected)
Pipe temperature too
low
• Correct boiler/mixing valve
temperature setting
• Ensure that the sensor is tight
to pipe and insulated.
• Verify power is connected to
heating cable.
• Confirm Low Temperature
Alarm (LTA) setting
Confirm HWAT-ECO settings
Confirm insulation schedule