3
Programming the Controller
34
EN-RaychemHWATECOcontroller-IM-H57340 03/13
TABLE 4: ADVANCED PROGRAMMING MENU
1 Time and
Date
1 Year
2 Month
3 Day
4 Hour
5 Minutes
Select Year
Select Month
Select Day
Select Hour
Select Minutes
2 Setup
(enter pass-
word if Lock
is ON)
1 Main Temp
“Enter maintain temp. setpoint”
2 Economy Temp
“Enter economy temp. setpoint”
3 Ambient Temp
“Enter ambient temp.”
4 Power Correction
Selectable
5 Lock
Lock/unlock Setup and Timer
menus
6 BMS
Select Yes/No
7 Network Master
Select Yes/No
8 Reinitialize
Select Yes/No
9 Short heater
Select Yes/No
10 LTA
(Low Temp Alarm)
1. Set Status
2. Set Temperature
3. Set Alarm Filter Time
4. Set Deadband
Select Yes/No
Enabled or Disabled
95°F (35°C) min
5-30 Minutes
4-18°F (2-10°C)
11 HTC
(High Tem. Cut Out)
1. Set Status
2. Set Temperature
3. Set Alarm Filter Time
4. Set Deadband
Enabled or Disabled
Maximum 205°F
10-30 Minutes
4-18°F (2-10°C)