MicroTrans
EQ
Operation & Maintenance Manual
Paragon Controls Incorporated
9
Revision Level 012
5. COMMON STARTUP CONFIGURATION CHANGES
5.1. AREA
FACTOR
The Area Factor can be entered or modified as follows:
Step 1.
From the active display, enter the Tech. Configuration Menu by pressing the Up/Down
keys simultaneously.
Step 2.
Enter password number 1000 and press the Enter key.
Step 3.
Press the Enter key once to access the Area Factor Menu.
Step 4.
Enter the new Area Factor using the Up/Down/Left/Right keys.
Step 5.
Press the Enter key once.
Step 6.
Press the ESC key twice.
Step 7.
The active display should now be displayed.
Tech. Config.
Password: 1000
Area Factor
Area Factor
Min Calibration
(FT
2
)
Span Calibration
Altitude
(001.000)
If the new Area Factor causes the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Area Factor Example below.
Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)