9. TECH CONFIGURATION MENUS
To set parameters under the Tech Configuration Menu, refer to the procedure below, associated
subsections and Section 6.3 for Key functions.
Step 1.
Enter the Tech Configuration Menu by pressing and holding the Up/Down Keys
simultaneously for 5 seconds.
Step 2.
Using the Up/Down/Left/Right Keys, enter password number 1000 and press the
Enter Key.
Step 3.
Once in the Tech Configuration Menu, use the Up/Down Keys to highlight the
required parameter for configuration as shown in Sections 9.1 through 9.13. Press
the Enter Key once to access the highlighted parameter Menu.
Step 4.
Once in the parameter menu, the parameter can be changed using the
Up/Down/Left/Right Keys. After the parameter has been changed, press the Enter
Key once. Then Press the ESC Key once to return to the Tech Configuration
Menu.
Step 5.
After all of the required parameters have been configured, exit the Tech
Configuration Menu by pressing the ESC Key. The Process Display (see Section
6.2) will then be displayed.
9.1. AREA
FACTOR
The Area Factor Menu allows the user to enter or modify an existing Area Factor. The Area Factor
Menu is only available if the MicroTrans
EQ
is configured by Paragon at the time of order for flow or
velocity and for input from a non-amplified Pitot-type flow sensor.
Tech. Config.
Password: 1000
Area Factor
Area Factor
Min Calibration
(FT
2
)
50% Calibration
Span Calibration
(001.000)
If the new Area Factor causes the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Area Factor Example below.
Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)