MicroTrans
EQ
Operation & Maintenance Manual
Paragon Controls Incorporated
19
Revision Level 012
8.4.2. Lockdown
Delay
The Lockdown Delay Menu allows the user to enter a lockdown time delay (0-20 seconds) that will
delay the display and output lockdown from occurring until the flow value or output value has remained
below the lockdown value for that duration.
Field Setup
Menu
Operating Range
Lockdown (0-20%)
Zero Calibration
(10)%
Engineering Units
Delay (0-20 sec)
Lockdown
(2) Sec
8.5. FLOW
CORRECTION
The Flow Correction Menu was incorporated into the MicroTrans
EQ
to give the user an easy way to
make corrections to the display and output without changing the Op. Range Value entered by the factory
or user. The Flow Correction Menu would be used to correct for a constant error from zero to the
entered Op Range Value. The following menus are only available if the MicroTrans
EQ
is configured by
Paragon at the time of order for flow or velocity.
8.5.1. Flow
Correction
(K-Factor)
If the user knows the % change required to match the balancers reading, select the K-Factor Menu and
enter this value for the K-Factor. The minimum and maximum allowable K-Factor Value is displayed in
the K-Factor Menu.
Field Setup
Menu
Flow Correction
Flow Correction
AutoZero
K-Factor
K-Factor Range
Temp Comp.
(0.85 / 1.3)
Display Filter
K-Factor Calc.
K=(01.000)
8.5.2. Flow Correction (K-Factor Calculator)
If the new K-factor Value needs to be calculated, select the K-Factor Calc. Menu, enter the
MicroTrans
EQ
Displayed Value and actual Measured Value, press Enter and the % change will be
calculated and stored as the new K-Factor Value.
Field
Setup
Menu
Flow Correction
Displayed Value
AutoZero
K-Factor
(000,000)
Temp Comp.
Measured Value
Display Filter
K-Factor Calc.
(000,000)