Operation & Maintenance Manual
Paragon Controls Incorporated
32
Revision Level 012
9.8.1. Probe
Coefficient
The Probe Coefficient Menu allows the user to modify the formula constant of 1096.70 for a non-
amplified Pitot-type flow sensor.
Tech. Config.
Password: 1000
Temp. Fixed Value
Correction Coeff.
Altitude
Probe
Output Calibration
(1096.70)
Correction Coeff.
(001,096.70
The probe coefficient entered into the MicroTrans
EQ
is based on the following equation:
∆
Where:
= Velocity (afpm)
= Non-amplified Pitot-tube Coefficient, 1096.70
∆
= Differential Pressure Measured by the Pitot-tube (in. w.c.)
= Actual Density (lb/ft
3
)
9.8.2. Piezometer Ring Coefficient
The Piezometer Ring Coefficient Menu allows a user to enter the correction coefficient associated with
the piezometer ring or amplified differential pressure flow sensor. Correction coefficients should be
obtained from the sensor or air handling unit manufacturer.
Tech. Config.
Password: 1000
Temp. Fixed Value
Correction Coeff.
Altitude
Piezometer Ring
Output Calibration
(000000.00)
Correction Coeff.
The piezometer ring coefficient entered into the MicroTrans
EQ
is based on the following equation:
∆
Where:
= Flow (acfm)
= Piezometer Ring Coefficient
∆
= Differential Pressure Measured by the Piezometer Ring (in. w.c.)
= Actual Density of Air (lb/ft
3
)