PROCESS OUTPUT FILTER
The Process Output Filter Menu allows the user to adjust the Process Output Filters rolling average
algorithm by setting the Sample Interval Time value in seconds and the number of rolling average
Sample Counts. The adjustment range of the Sample Interval Time is 0.10 to 65.5 seconds in 0.10
increments. The Sample Count range is 0 to 150 Sample Counts. The Process Output Filter is
independent of the Display Filter Value (See Section 8.8).
Field Setup
Menu
Output Filter
Sample Interval Time
Alarm Options
(00.5)sec.
DP Display Format
(0-150) Sample Count
Factory Defaults
(010)
8.10. HIGH/LOW
ALARM
OPTIONS
The following menus for configuration of High/Low Alarms are only available if the High/Low Alarm
option is purchased.
8.10.1. Alarm Status
The Alarm Status allows the user to independently turn each alarm ON or OFF.
Field
Setup
Menu
Output Filter
Alarm Status
Low Alarm
Alarm Options
Alarm Value
(On)
DP Display Format
Alarm Delay
High Alarm
Factory Defaults
(On)