TROUBLESHOOTING TABLE
SYMPTOM
SOLUTION
6. Continued
4. If the Temperature Compensation Option is
installed, verify correct temperature input signal.
Verify that the temperature input is connected
correctly.
5. Contact
Factory
7. Incorrect Temperature Reading
1. Verify Temperature Transmitter specifications
match with MicroTrans
EQ
ID Label
(Current/Voltage, Temperature Range)
2. Verify Temperature Transmitter is connected
correctly to the MicroTrans
EQ
(see Section 3.2).
3. Verify Temperature Transmitter signal at the
MicroTrans
EQ
connector J2 is correct.
4. Contact
Factory
8. No Output signal or Incorrect Output
signal. Display is reading correct
value.
1. Verify Process Output S2 & S4 switches are in the
correct position for the application (see Section 4.1
and the figure in Section 3.1.
2. Disconnect Output signal wires and verify output
signal at MicroTrans
EQ
connector J2 is correct.
3. Verify correct Operating Range (see Section 5.2)
4. Perform Output Cal (see Section 9.7)
5. Contact
Factory
9. Incorrect Process Output Values after
changing Area Factor, Altitude, or
Temperature Value. Display readings
are correct.
1. Re-Enter Operating Range Value in Field Menu
(see Section 5.2)
2. Contact
Factory
10. Unstable Display and Process Output
at very low flow.
1. Increase Display and Process Filter
2. Decrease Lockdown Value
3. Increase Lockdown Delay Value
4. Contact
Factory
11. “AZ Error” text on display
1. Turn Power Switch S3 Off and On to reset the
AutoZero valve
Summary of Contents for MicroTrans EQ