MicroTrans
EQ
Operation & Maintenance Manual
Paragon Controls Incorporated
29
Revision Level 012
9.3. 50%
CALIBRATION
The 50% Calibration Menu is only available when the MicroTrans
EQ
is configured by Paragon at the
time of order for pressure; it allows a user to perform a 50% transducer calibration to eliminate zero drift
in a bipolar transducer. This value will be placed in a different memory location and used until a Return
to Factory Defaults is selected (see Section 8.12).
Tech.
Config.
Password:
1000
Area Factor
Input Value
CPU
Taking
Min Calibration
(0.0285) inch w.c.
Samples
50% Calibration
Span Calibration
(Press Enter)
(Please
Wait)
9.4. SPAN
CALIBRATION
The Span Calibration Menu allows the user to perform a span transducer calibration to eliminate any
possible transducer drift. This value will be placed in a different memory location than the Factory Span
memory location and used until a Return to Factory Defaults is selected (see Section 8.12).
Tech.
Config.
Password:
1000
Area Factor
Input Value
CPU
Taking
Min Calibration
(0.0570) Inch w.c.
Samples
50% Calibration
Span Calibration
(Press Enter)
(Please
Wait)
9.5.
TEMPERATURE FIXED VALUE
When the Temperature Compensation option (see Section 8.7) is not ordered, the Fixed Value Menu
allows the user to enter a temperature value other than the standard value of 68
˚
F for the density
calculations. This value will not be displayed on the LCD screen.
Tech. Config.
Password: 1000
Temp. Fixed Value
Temp. Fixed Value
Altitude
ºF
Output Calibration
(+068)
Correction Coeff.