![PCI MicroTrans EQ Operation & Maintenance Manual Download Page 24](http://html1.mh-extra.com/html/pci/microtrans-eq/microtrans-eq_operation-and-maintenance-manual_1516232024.webp)
MicroTrans
EQ
Operation & Maintenance Manual
Paragon Controls Incorporated
20
Revision Level 012
-FLOW CORRECTION EXAMPLE-
The balancer is consistently measuring a value of 9,500 CFM, which is 500 CFM less than the 10,000
CFM value on the MicroTrans
EQ
display. The user would then perform the following math function:
Measured Value / Displayed Value = K-Factor so 9,500 CFM / 10,000 CFM = 0.950. The user would
enter 0.950 for the K-Factor Flow Correction. If the K-Factor Calculator is used, the K- Factor Flow
Correction would automatically update the K Factor.
8.6. AUTOZERO
The AutoZero option detects and corrects any zero offset caused by large ambient temperature changes.
The following menus for configuration of AutoZero are only available if the AutoZero option is
purchased.
8.6.1. AutoZero
Status
The AutoZero Status Menu allows the user to turn the AutoZero function ON or OFF.
Field
Setup
Menu
Flow Correction
AZ Status
AZ Status
AutoZero
AZ Interval
(ON/OFF)
Temp Comp.
AZ Test Interval
Display Filter
(ON)
8.6.2. AutoZero
Interval
The AutoZero Interval Menu allows the user to select the AutoZero Interval from once an hour to once a
day in 1 hour increments. Use the UP/DOWN keys to select the interval value. Upon device power up,
an AutoZero cycle will occur after 20 seconds.
Field
Setup
Menu
Flow Correction
AZ Status
AZ Interval
AutoZero
AZ Interval
(1 TO 24HR)
Temp Comp.
AZ Test Interval
Display Filter
(1)HR