Figure 30 CANopen Network for ACR90x0
ACR90x0 CANopen Pinout (Minimum)
Pin
Description
Wire Color
2
Connect to CAN_L on slave node(s)
White
7
Connect to CAN_H on slave node(s)
Blue
3
Connect to CAN_GND on slave node(s)
Black
Notes
CANopen recommends that all nine wires on the connector be routed to support future
network enhancements. The signals listed above are the minimum required for the
ACR90x0.
CAN_H and CAN_L should be a twisted-cable pair with a third wire run as a common ground
between nodes. If all network nodes implement isolation, CAN_GND is optional.
Connection is recommended if the network contains non-isolated nodes.
Use shielded cabling to improve network noise immunity. See Appendix on page
Error!
Bookmark not defined.
.
The conductor shield of the cable may be routed to pin 5, CAN_SHLD, which is terminated
with 1M
Ω
resistor to protective earth. If required, make a low ohmic connection of the
shield to the protective earth through the metal D-sub back shell.
Table 49 CANopen Pinout (Minimum)