52
Requirements and Guidelines for UL INSTALLATIONS
UL has only evaluated the 708, 728, 728 EXPRESS, 738, 738 EXPRESS, 748 and 748ES for compatibility
with the Ademco model 685, FBI model CP220FB, SUR-GUARD SG-MLR2-D6 and Silent Knight model 9000.
UL listed in accordance with standard
UL1023
(Household Burglar - Alarm System Units), standard
UL985
(Household Fire Warning Units) and
UL1635
(Digital Alarm Communicator System Units).
Look for the
mark on the product. Only products bearing this mark are UL listed.
Some operational features are not permitted in UL installations. To respect the standards for household
applications, the installer should follow these guidelines when configuring the system.
1.
ALL components of the system should be UL listed for the intended application.
2.
If the installation is a FIRE ALARM application, refer to NFPA Standard 74 for details on smoke detector
locations. There must be at least one UL-Listed Indoor Fire Alarm Warning Signaling Appliance.
3.
For UL Burglar Applications:
Maximum entry time = UL 45 seconds
Maximum exit time = UL 60 seconds
Minimum bell cutoff time = 4 minutes
4.
Keypad Models 636, 646 and 642, are not UL listed.
5.
The upload/download software should not be used on UL listed systems.
6.
All outputs are Class 2 or power-limited, except for the battery terminal. The Class 2 and power-limited
fire alarm circuits shall be installed using CL3, CL3R, CL3P or substitute cable permitted by the National
Electrical Code, ANSI/NFPA 70.
Requirements and Guidelines for AUSTEL INSTALLATIONS
Austel-approved installations: use a transformer approved by the State Electricity commission, such as
"Dyen" PA series 15VAC 22VA. With this transformer, do not exceed the following maximum currents:
- maximum Auxiliary current (including keypads): 300mA
- maximum Bell current :600mA
Summary of Contents for Esprit 748