26
518 -
Partial Arming:
Whenever the system is "Away" armed, "Stay" armed, or armed
while one or more zones are bypassed.
519 -
Recent Close:
An alarm occurs shortly after the system has been armed, refer to
Recent Close Delay
in section 6.10.
520 -
Duress:
The Duress feature is enabled (see section 3.4) and a User disarms the
system using the User Code #48.
524 -
Log-In (Espload):
Espload software is used to communicate with the Control Panel.
525 -
Program Change:
The installer code is used to enter the programming mode
521 to 523 -
Reserved for Future Use
526 to 527 -
Reserved for Future Use
6.7
Auto Test Report
Decimal Programming
?
Addresses 046-048
Default: Auto Test Report Disabled
The report code programmed at address 512 will be reported to the central station after the number
of days programmed at address 046 and the time programmed at address 047 (hours) and 048
(minutes) has elapsed. To disable this feature, program 000 at address 046. Also note that if
[2
ND
][2
ND
] is programmed at address 512 nothing will be reported.
[
ENTER
]
+
Installer Code
+
[10] [4] [6]
+
3 digits (days)
+
[10] [4] [7]
+
3 digits (hours)
+
[10] [4] [8]
+
3 digits (minutes)
+
[
ENTER
]
6.8
Manual Test Report
Key Access Programming
?
key [
BYP
]
Activating the manual test report will send the Event Code programmed at address 512 to the
Central Station.
[
ENTER
]
+
(Installer, Master, or User 1 Code)
+
[
BYP
]
+
[
ENTER
]
6.9
Power Failure Report Delay
Decimal Programming
?
Addresses 054
Default: 30 minutes
After a power failure, the control panel will delay transmission of the event code programmed at
address 499 by the period programmed at this address (001 to 255 minutes).
[
ENTER
]
+
Installer Code
+
[10] [5] [4]
+
3-digit decimal value (001-255)
+
[
ENTER
]
6.10 Recent Close Delay
Decimal Programming
?
Addresses 060
Default: Recent Close Delay Disabled
The system will transmit the recent close event code programmed at address 519 if after arming
the system, an alarm occurs within the period programmed at this address (001 to 255 minutes).
Program 000 into address 060 to disable this feature.
[
ENTER
]
+
Installer Code
+
[10] [6] [10]
+
3-digit decimal value (001-255)
+
[
ENTER
]