43
10.7 Tamper/Wire Fault Recognition Options
Feature Select Programming
?
Address 088, keys [10] to [11]
If the control panel detects an open or a short on a zone when the system is armed, regardless of
the tamper/wire settings it will always generate an alarm and trouble indicator (key [9]). Alarms will
be audible or silent depending on individual zone definitions. If an open or short occurs on a
disarmed system, the control panel will generate an incident depending on the following settings:
"Tamper/wire" disabled
Tamper/wiring failure recognition is disabled. Not permitted on UL listed systems.
"Trouble" enabled
Tamper/wiring failure will generate a trouble indicator (key [9]) and a trouble report code (see
Tamper/Trouble Codes
in section 6.6.6.) when the system is disarmed.
"Silent alarm" enabled
Tamper/wiring failure will generate a trouble indicator (key [9]), a trouble report code (see
Tamper/Trouble Codes
in section 6.6.6.) and a silent alarm (no bells/sirens)
"Audible alarm" enabled
Tamper/wiring failure will generate a trouble indicator (key [9]), a trouble report code (see
Tamper/Trouble Codes
in section 6.6.6.) and an audible alarm.
Exception! When the zone definition is "24 hour", the tamper definition follows the
audible/silent alarm definition of the "24 hour" zone.
10.8 Tamper Bypass Options
Feature Select Programming
?
Address 090, key [6]
With this option enabled, the control panel will
not
generate an alarm if a tamper is detected on a
bypassed zone while the system is armed. With this option disabled, the control panel will generate
an alarm if a tamper is detected on a bypassed zone while the system is armed.
Key [6] "Off": Arm the system if Tamper on Bypassed Zone
Key [6] "On": Do not arm the system if Tamper on Bypassed Zone
[
ENTER
]
+
Installer Code
+
[10] [9] [10]
+
[6]
On/Off
+
[
ENTER
]
10.9 Installer Test Mode
Key Access Programming
?
key [8]
The "Test Mode" will allow you to perform walk tests where the bell or siren will squawk, to indicate
opened zones. To enter or exit the control panel "Test Mode" press:
[
ENTER
]
+
Installer Code
+
[8]
to enable; press
[8]
again to disable