Logical AND Inputs
Logical AND requires
ALL
of the selected inputs to the logic to be in a triggering
state to activate the relay logic.
Logical OR Inputs
Logical OR requires only ONE of the selected inputs to be in a triggering state to
activate the relay logic.
Delay Timer On
Specifies the time in seconds which must elapse before the logic activates in a
situation where it would otherwise activate immediately.
This is useful in a situation where you want a delay to be added before a logic
controlled relay is switched on.
If the logic triggering condition clears before the specified time has elapsed then the
logic will not activate at all.
Delay Timer Off
Specifies the time in seconds which must elapse before the logic deactivates in a
situation where it would otherwise deactivate immediately.
This is useful in a situation where you want a delay to be added before a logic
controlled relay is switched off from a current on state.
If the logic triggering condition returns before the specified time has elapsed then the
logic will not deactivate at all.
Final Invert
A final invert check box is provided. This allows the final output logical state to the
relay to be inverted.
Essentially, any conditions which produce a relay on output will produce the reverse