RMS Compact II
Version 1.0.7 September 2016
Page 46
Relays
– Configure - Config
Actual Digital Output Relay logic configurations are specified here.
Figure 4-16.
Relay Specific Configuration
Input Selection
Inputs into the logic are selected on the left hand side by clicking one of the
Click to
Enable
boxes.
Here a sensor type, threshold and channel can be chosen to feed into logic.
Invert
The Invert checkbox allows the logic inversion of an input into the logic.
For example, an upper warning limit is breached, this yields the follow input into
logic.
No Invert
Invert
Threshold breached
1 (Logic Triggering)
0 (Not Logic Triggering)
Threshold within limit
0 (Not Logic Triggering)
1 (Logic Triggering)
Table 4-2.
Input Logic Inversion.
Logic Operator
Logic Operator provides options which control the evaluation of inputs to logic.