RMS Compact II
Version 1.0.7 September 2016
Page 37
Input Sensors
– Defaults
The Input Sensor Defaults menu allows configuration parameters which relate to input
sensors of specific types to be defined and applied to all inputs of that type.
The types of input sensors are:-
Temperature
Humidity
Open/Close Contacts (digital inputs)
Figure 4-10.
Input Sensor Defaults with Temperature and Humidity menus.
The defaults than can be specified are described below.
Calibration Offset
The value entered here alters the actual reading of a sensor by the amount specified.
For example, if an Calibration offset of 6 was used and a sensors true reading was 36
the indicated reading used for display and alarm purposes would be 42.
This works in an identical way for both temperature and humidity sensors.
Hysteresis Value
The hysteresis default value to be applied to sensors is specified here. The value
specified is an offset from a sensors threshold values.