RMS Compact II
Version 1.0.7 September 2016
Page 44
Relays
– Configure
Relay and logic configuration is performed via two pages.
Figure 4-15.
Relay Configure
Name
Relay output name is specified here. (E.g. Fan_Tray or Door_1).
Normal State
Normal State specifies the ‘normal’ or ‘non-alarm’ state of a relay.
Not Active
Specifies that a output relay in a ‘Not Active’ (‘not-energised’) state is normal.
Active
Specifies that an output relay in an ‘Active’ (‘Energised’) state is normal.
Trap Enabled
Toggles alarm trap generation. An alarm trap will be generated when the relay is in an
‘alarm’ state with this enabled.
Repeat Timer
Specifies an interval in which a trap for an
existing
alarm condition will be
regenerated. This will be a duplicate of the original trap. A repeat timer is not
necessary in NMS systems employing intelligent trap handling. Setting zero (0)
disables repeat traps.
Controlled