9-2-3. S uspending th e Indoor U nit
D epending on the ceiling typ e:
1. Check the suspension b olt pitch.
2. Ensure that the ceiling is strong enough to support the w eight of the unit.
3. To preve nt the unit f rom dropping, f irmly f asten the suspension b olts as show n in the f igure b elow .
L*
20 ~
50
Hole- in- anchor
Hole- in- plug
Insert
U nit: mm
Concrete
Suspension b olt
(f ield supply)
Hexagonal nut (f ield supply)
Special w asher (f ield supply)
Special w asher (f ield supply)
Hexagonal nut (f ield supply)
Suspension b olt (f ield supply)
Hexagonal nut (f ield supply)
Special w asher (supplied)
Suspension lug
* Choose “L” dimension according to the status of the ceiling.
Fig. 1-18
Fig. 1-19
N O T E
Suspension b olt
(f ield supply)
M10 or 3/8”
W A R N IN G
It is important th at you use extreme care in supporting th e indoor unit inside th e ceiling.
Ensure th at th e ceiling is strong enough to support th e w eigh t of th e unit.
B efore suspending th e unit, test th e strength of each attach ed suspension b olt.
(1)
W
hen placing the unit inside the ceiling, determine the pitch of the suspension b olts ref erring to the dimensional data giv en prev iously .
Tub ing must b e laid and connected inside the ceiling w hen suspending the unit.
If the ceiling is already constructed, lay the tub ing into position f or connection to the unit b ef ore placing the unit inside the ceiling.
(2) Screw in the suspension b olts allow ing them to protrude f rom the ceiling as show n in F ig. 1- 18. (Cut the ceiling material, if necessary. )
(3) Suspend and f ix the indoor unit using the 2 hexagonal nuts (f ield supply) and special w ashers (supplied w ith the unit) as show n in
F ig. 1- 19.
C A U TIO N
• T
h e top of th e unit must b e installed h orizo ntally.
Horizo ntal
leve l
• C
h eck th e unit is placed h orizo ntally.
M ak e sure th e unit is installed lev el using a lev el or a v inyl h ose filled
w ith w ater.
In using a v inyl h ose instead of a lev el, adj ust th e top surface of th e unit to
th e surface of th e w ater at b oth ends of th e v inyl h ose and mak e h orizo ntal
adj ustment on all 4 corners of th e unit.
If th e air disch arge side of th e unit is installed dow nw ard, splash ing w ater
or w ater leak may occur.
A lso, th e dust may accumulate inside th e drain pan caused b y draining
residual w ater.
• W
h en lifting th e unit, do not attempt to h old th e electrical component b ox in
h and.
• D
o not leav e th e drain pan of th e unit dow nw ard for long h ours.
If doing so, th e insulation material can b e crush ed.
C rush ed insulation can lead to condensation.
Carpenter’ s leve l
Vinyl hose f illed w ith w ater
Electrical component b ox
SM830262-00_大洋州向け シングル天埋_TD&SM.indb
18/01/26 13:2 :3
Summary of Contents for S-160PE1R5A
Page 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Page 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Page 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Page 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...