Outdoor U nit Control PCB (A CX A 7 3 -0 47 7 0 , A CX A 7 3 -0 47 5 0 )
Explanation of Functions
A. ADD pin
(2P, Black)
Auto address setting pin
Short-circuit this pin for 1 second or longer to automatically set the
addresses at the indoor units that are connected to that outdoor unit and
are within the same system.
The system address is " 0" at the time of shipment. Auto address setting
is necessary even for communications lines in a single system where the
inter-unit control wiring does not cross to any other systems.
While auto address setting is in progress, the 2 LEDs (LED1, 2: Red) on
the outdoor unit control PCB blink alternately. (Short-circuiting this pin
while auto address setting is in progress will stop the auto address setting
operation.)
SW2
Rotary switch
(10 positions, Y ellow) Outdoor system address setting switch
The setting is " 0" at the time of shipment. It is not necessary to change
the setting if wiring is connected only to an outdoor unit and indoor units
in a single system and the inter-unit control wiring does not cross multiple
systems.
If wiring links the inter-unit control wiring for multiple systems to the same
communications lines, then a different address must be set for each
refrigerant tubing system.
If wiring links multiple systems, a maximum of 30 systems (up to 64 indoor
units) can be connected. This setting can be set up to " 39 ," however
control will be for 30 systems even if the setting is set to higher than 30.
An alarm will be displayed if system addresses are duplicated.
(For details, see Table 4-1.)
SW1
DIP switch
(2P, Black)
Switches for setting system address 10s digit and 20s digit
If 10 systems or more are set, the setting is made by a combination of this
DIP switch and SW2.
If 10 - 19 systems are set, set switch 1 (10s digit) to ON.
If 20 - 29 systems are set, set switch 2 (20s digit) to ON, and set switch 1
(10s digit) to OFF.
If 30 systems are set, set both switch 1 (10s digit) and switch 2 (20s digit)
to ON.(For details, see Table 4-1.)
PUM P DOWN (2P, Black)
Refrigerant recovery Pin
Short circuit this pin to perform refrigerant recovery control using cooling
operation. The indoor unit fan will operate at H IG H and 60H z for a maximum
of 10 minutes When refrigerant recovery is completed, close the valves
and open circuit this pin to stop the operation.
LED 1
LED 2
(D302)
(D303)
LED (red × 2)
LED 1 and 2 blink alternately while automatic address setting is in progress.
Display the alarm contents for alarms that are detected by the outdoor unit.
RUN
(2P, Black)
Start pin
Short-circuit this pin and apply a pulse signal to start all indoor units in that
refrigerant system.
Stop
(2P, Black)
Stop pin
Short-circuit this pin and apply a pulse signal to stop all indoor units in that
refrigerant system.
M ode change (3P, Black)
Indoor unit H eating/Cooling mode change pin
Short-circuiting this pin during ordinary operation changes the mode from
Cooling to H eating (if the current mode is Cooling) or from H eating to
Cooling (if the current mode is H eating).
Test
(2P, Black)
This pin is used to test the PCB at the factory.
When the power is turned ON after this pin has been short-circuited, all
output signals will be output in sequence. (Sequential output does not
occur if this pin is short-circuited when the power is already ON.) Releasing
this pin returns the unit to normal control.
CH K
(2P, Black)
Short-circuit during the test run operation.
Open the circuit after the test run.
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 10
18/01/12 18: 2:31
Summary of Contents for S-160PE1R5A
Page 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Page 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Page 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Page 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...