7
7
Optional Controller
Remote Controller Functions
2. Test Run Function
A
°
°
7-8. Test Run Function
Fig. 7-4
Operates the unit with the thermostat forced ON.
Press and hold the button for 4 seconds or
longer.
“ ” appears on the remote controller LCD
display (Fig. 7-4).
Press the button to start the test run.
The temperature cannot be adjusted in Test Run mode.
(This mode places a heavy load on the machines.
Therefore use it only when performing the test run.)
The test run can be performed using the HEAT, COOL,
or FAN operation modes.
The outdoor units will not operate for
approximately 3 minutes after the power
is turned ON and after operation is stopped.
If correct operation is not possible, an error code is
displayed on the remote controller LCD display.
To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after
60 minutes.
The operation is possible even if the cassette-type ceiling panel has not been installed.
(“P09” display does not occur.)
Press the button to return to normal remote controller display.
(1)(4)
(3)
(2)
(1)
(2)
(3)
(4)
NOTE
The temperature display appears as “- - - -” for units that are not connected.
*
If monitor mode is engaged while normal operation is in progress, only the parts of the LCD display shown in
the figure will change. Other parts continue to display the same information as during normal operation.
Fig. 7-5
A
°
°
Press and hold the and buttons
simultaneously for 4 seconds or longer.
The unit No. “X-X” (main unit No.), item code “ ”
(sensor address), and servicing monitor “ ”
(sensor temperature) are displayed on the remote
controller LCD display. (See Fig. 7-5 at right.)
Press the temperature setting / buttons
and select the item code to the address of the
sensor to monitor.
If group control is in effect, press the button
to select the unit to monitor.
Press the temperature setting buttons to select the
item code to change.
Press the button to return to normal remote
controller display.
(3)(4)
(5)
(1)
(4)
(3)
(4)
(2)
(1)
(2)
(3)
(4)
(5)
Sensor Temperature Display Function
(displayed regardless of whether unit
is operating or stopped)
The procedure below display the sensor temperatures
from the remote controller, inddor unit, and outdoor
unit on the remote controller.
Item code
M eaning of Code
Indoor unit data
02
Indoor unit intake temp.
03
Indoor unit heat exchanger temp. (E1)
04
Indoor unit heat exchanger temp. (E2)
05
–
06
–
07
–
08
–
09
Outdoor unit data
0A
Discharge temp. (TD)
0b
–
0C
–
0d
Intake temp. (TS)
0E
Outdoor unit heat exchanger temp. (C1)
0F
Outdoor unit heat exchanger temp. (C2)
10
–
11
Outdoor air temp. ( TO )
12
–
13
Current value (CTL2)
14
Current value (CTL1)
15
Outdoor M V value (M OV 1)
16
–
19
Frequency
* Depending on the model, some items may not be displayed.
7-15
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 1
18/01/2 17:42:12
Summary of Contents for S-160PE1R5A
Page 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Page 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Page 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Page 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...