1-30
1
1
External S tatic Pressure S etting
Type E3
Choose one of the methods (selection of “a”, “b”, “c” within the range of dotted line as shown in the flowchart below)
and make settings.
a. N o setting changes:
W
hen using as it is f actory preset at shipment.
(If resetting after external static pressure setting once, it might be different from factory preset.)
b .
Manual setting (on PCB):
This is static pressure setting excepting f actory preset at shipment. D ip sw itch select method.
c.
Manual setting (by timer remote controller):
Static pressure setting excepting f actory preset at shipment.
Flow of External S tatic Pressure
N O T E
(1)
See the Tab les 1- 2, 1- 3 and F ig. 1- 2 f or details on the relationship b etw een the va lue of item code “5d” and the
external static pressure.
(2) When set in group control (connecting multiple indoor units with one timer remote controller), set each indoor
unit to item code “5d”.
When amending the setting after selecting [ b. Manual setting] (due to airflow path changes, etc.), it is
necessary to cancel [b. Manual setting] (switching OFF positions).
W
hen [ b . Manual setting] has not b een cancelled, [ c. Manual setting] w ill b e activa ted if selected, b ut [ b . Manual
setting] take s precedence w hen the pow er is sw itched b ack on af ter pow er outages, etc.
M ak e sure th e external static pressure is in a range of specifications.
Th en proceed th e external static pressure setting.
Improper settings can cause noise, a sh ortage of airflow v olume and w ater
leak age.
S ee th e Fig. 1-2 for th e external static pressure setting range.
B e sure to set th e [ External S tatic Pressure S etting] once again after amending
th e airflow path for th e duct or air outlet after setting th e external static pressure.
Start of external static pressure setting
Setting of shipment : line 5
Is it designed
and installed at the setting
line at shipment on
PQ line draw ing?
See the section
1- 9- 4.
O perating b y
timer remote
controller
Selection methods
of external static
pressure setting
N o
N o
Y es
Y es
a. N o setting ch anges
b . M anual setting
(Setting on PCB)
Setting sw itches of TP6 or
TP3 or TP1
See the section " 1- 9- 1. How to
Set on PC B oard" .
c. M anual setting
Item code 5d : Setting 1, 3, 6
(*Note 1) (*Note 2)
See the section 1- 9- 2. or 1- 9- 3.
Completion of external static pressure setting
C A U TIO N
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 30
18/01/26 13:2 :2
Summary of Contents for S-160PE1R5A
Page 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Page 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Page 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Page 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...