8
8
1. The Self-Diagnosis Function Display and What is Detected
8-16. Common to All Models
Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote controller is
connected. For information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or to
Test Run or servicing materials.
: Off /
: On /
: Blinking (0.5 sec. intervals)
Error Detected
WL Remote Controller LED Displa
y
Alarm Display
Run
Timer
Standby
Blinking
Communication error in the remote
controller circuit
E01–E03, E08–E14, E17, E18
Communication error either in the in/
outdoor operation line or the sub-bus of
the outdoor unit
E04–E07, E15, E16, E19–E31
Operation of indoor protection device
P01, P09–P14
Alternately
Operation of outdoor protection device
P02–P08, P15–P31
Alternately
Error in the indoor thermistor
F01–F03, F10–F11
Alternately
Error in the outdoor thermistor
F04–F09, F12–F28
Alternately
Error in the indoor EEPROM
F29
Simultaneously
Error in the outdoor EEPROM
F30, F31
Simultaneously
Error related to the compressor
H01–H31
Error in indoor settings
L01–L03 L05–L09
Simultaneously
Error in outdoor settings
L04, L10–L31
Simultaneously
Inconsistency in Air/Heat (Including an auto-temp setting for a model without
auto-temp settings)
Alternately
Oil Alarm (Same as operation of outdoor protection device)
Alternately
Test Run
Simultaneously
Sensor Button
2. Room Temperature Sensor Settings
Common to All Models
The indoor unit and the wireless remote controller are equipped with
indoor temperature sensors. The sensing of indoor temperature
works via one of them.
When the unit is shipped, it is set to the indoor unit, but to switch
to the remote controller, press the sensor button (diagram at right)
inside the remote controller’s cover and then check to make sure that
Main Sensor on the LCD screen goes off.
Even when the Sensor switch has been set to the remote
controller, if the unit does not receive any room temperature
data from the remote controller for ten minutes, it automatically
switches back to the indoor unit sensor, so be sure to install
the remote controller facing the receiver.
NOTE
Fig. 8-10
3. Setting Up Remote Controller Functions
The operation of the air conditioner can be impacted, depending on the settings made, so only service personnel
should make the settings.
Furthermore, making changes to these settings may cause actual operation to deviate from what is printed in the
Users Manual, so be sure to explain this to the customer fully.
Making Settings (Do with unit stopped)
(1) Holding down the Swing/Wind Dir OFF Timer + Mode Select buttons at the same time for 4 or more
seconds makes the Display switch to the setting screen. (See diagram below.)
(2) Use the Temperature setting buttons,
, to select the number of the item to be set.
(3) Use the ON Timer buttons,
, to change settings.
(4) The settings are saved with the Once/Every Day button. When this is done, the settings display of the LCD
changes from blinking to light.
(5) If other settings are to be changed as well, repeat steps 2 to 4.
(6) When all settings have been made, press the Start/Stop button.
Example: Operation mode setting screen
Item Number & Setting Item
Setting Content
Setting when
Shipped
1
Operation Mode
2
Flap Display
3
Select Fan Speed
4
Display of Set
Temperature
°C
°F
Setting Off (Note 2)
°C
5
Time Display
24 Hour (No Display)
AM/PM
24 Hour
6
Ventilation Fan ON/OF F Off (No Display)
On
OFF(Note 3)
7
Cool temp Max
05 – 35°C
30
8
Cool temp Min
05 – 35°C
18
9
Heat temp Max
05 – 35°C
26 (Note 4)
10 Heat temp Min
05 – 35°C
16
11 Dry temp Max
05 – 35°C
30
12 Dry temp Min
05 – 35°C
18
13 Auto temp Max
05 – 35°C
27
14 Auto temp Min
05 – 35°C
17
16 Address Setting Max
Value
00 (ALL only)
01 – 31
06 (Note 5)
17 Heat temp Max ON/OFF JP (Heater Max Temp Change Off)
EP (On)
JP
(1)
(4)
(3)
(2)
(6)
(Note 1)
(No Display)
(No Display)
Item
Number
/
/
(1) While the unit is in the swinging mode (Swing/Wind Direction), the flap cannot be stopped in a desired position.
(2) When Setting OFF is selected, "°C" is displayed on the LCD screen.
(3) You can toggle between ON and OFF by pressing Ventilation for 4 seconds or more.
(4) If the Heater Max ON/OFF setting is not changed to EP (ON), the setting change will not be reflected.
(5) This is the number of addresses that can be set in the address change mode. Do not set it to 07 or above.
The functions of the wireless remote controller can be set on site.
(These settings are saved in nonvolatile memory in the remote controller, so even when its batteries are changed,
the settings do not revert to the defaults.)
NOTE
NOTE
8-21
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 21
17/12/27 14:24:31
Summary of Contents for S-160PE1R5A
Page 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Page 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Page 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Page 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...