7
7
7-2. List of Simple Setting Items
Item code
Item
Setting data
No.
Description
Filter sign ON time
(filter life time)
0000
Not displayed
0001
150 hours
0002
2,500 hours
0003
5,000 hours
0004
10,000 hours
0005
Use the filter clogging sensor.
Degree of filter fouling
0000
Standard (setting at time of shipping)
0001
Highly fouled
(Filter sign ON time is reduced to one-half the set time.)
Central control
address
0001
Central control address 1
0002
Central control address 2
0003
Central control address 3
0064
Central control address 64
0099
No central control address set (setting at time of shipping)
Operating mode
priority change
0000
Normal ( setting at time of shipping)
0001
Priority
Fan speed when
heating thermostat is
OFF
Compressor ON
Compressor OFF
0000
Lo 1 min., LL 3 min.
LL
0001
Lo
LL
0002
LL
LL
0004
Lo 1 min., LL 3 min.
Lo
0005
Lo
Lo
0006
LL
Lo
Heating intake
temperature shift
0000
No shift
0001
Shifts intake temperature 1 °C down.
0002
Shifts intake temperature 2 °C down.
0003
Shifts intake temperature 3 °C down.
0004
Shifts intake temperature 4 °C down.
0005
Shifts intake temperature 5 °C down.
0006
Shifts intake temperature 6 °C down.
Electric heater
installation
0000
No heater
0001
Heater installed
Humidifying when
heater thermostat is
OFF
0000
No (setting at time of shipping)
0001
Yes
Permit/prohibit
automatic
heating/cooling
0000
Permit
0001
Prohibit
Cool-only
0000
Normal
0001
Cool only (Set “1” for item code OD.)
NOTE
•
In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF
unless a vaporizing humidifier is used.
•
Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
•
Do not change any setting data that does not appear in this list.
Optional Controller
Remote Controller Functions
4. Simple Settings Function
A
°
°
This allows the filter lifetime, operating mode priority change, central control address, and other settings to be
made for an individual or group-control indoor unit to which the remote controller used for simple settings is
connected.
When simple settings mode is engaged, operation stops at the individual or group-control indoor unit to which
the remote controller for simple settings is connected.
Press and hold the and buttons
simultaneously for 4 seconds or longer.
“ ”, unit No. “ ” (or “ ” in the case
of group control), item code “ ,” and settings
data “ ” are displayed blinking on the remote
controller LCD display (Fig. 7-1). At this time, the
indoor unit fan (or all indoor unit fans in the case of
group control) begins operating.
If group control is in effect, press the button and
select the address (unit No.) of the indoor unit to set.
At this time, the fan at the indoor unit begins operating.
* If unit No.“ ” is displayed, the same setting
will be made for all indoor units.
Press the temperature setting / buttons to
select the item code to change.
Press the timer time / buttons to select the
desired setting data.
* For item codes and setting data, refer to the
following page.
Press the button. (The display stops blinking
and remains lit, and setting is completed.)
Press the button to return to normal remote
controller display.
(7)
(1)
(6)
(3)
(2)
(4)
(5)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
7-3
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 3
18/01/2 17:42:08
Summary of Contents for S-160PE1R5A
Page 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Page 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Page 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Page 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...