Item code
Item
Setting data
No.
Description
Ventilation fan operation
0000
None
0001
Ventilation fan operated by remote controller.
Wired remote controller
sensor
0000
Not used. (Body sensor is used.)
0001
Remote controller sensor is used.
“Operation change control in
progress” display
0000
Normal (displayed)
0001
Not displayed
OFF reminder function for
when weekly timer is used
0000
None
0001
Only stop time setting is enabled.
Heat exchanger temperature
for cold air discharge
(Heat exchanger control
point for control to prevent
cold air)
0013
Control temperature 13°C
0014
Control temperature 14°C
0025
Control temperature 25°C
0026
Control temperature 26°C
Fan output switching
0000
Output linked with fan. (ON when indoor unit fan is operating.)
0001
Fan mode operation output
Fan tap setting
(External static pressure of
the rated air flow volume)
0001
Type 180: 60Pa
Type 200: 75Pa
Type 224: 75Pa
(Setting at shipment)
0002
Type 180: 100Pa
Type 200: 120Pa
Type 224: 130Pa
0003
Type 180: 150Pa
Type 200: 180Pa
Type 224: 200Pa
Repeat timer switching
0000
Function disabled
0001
Function enabled
Timer function change
prohibit
0000
Function disabled
0001
Function enabled
7-7
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 7
18/01/2 17:42:11
Summary of Contents for S-160PE1R5A
Page 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Page 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Page 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Page 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...